Register(s) | Meaning | Scale Unit | Data format | R/W |
---|---|---|---|---|
0000h-0001h | total energy | 1/100 kWh | unsigned dword | R¹ |
0002h-0003h | reserved | unsigned dword | ||
0004h-0005h | reserved | unsigned dword | ||
0006h-0007h | reserved | unsigned dword | ||
0008h-0009h | export energy | 1/100 kWh | unsigned dword | R¹ |
000Ah-000Bh | import energy | 1/100 kWh | unsigned dword | R¹ |
000Ch | voltage | 1/10 V | unsigned word | R |
000Dh | current | 1/100 A | unsigned word | R |
000Eh | active power | 1 W | signed word | R |
000Fh | reactive power | 1 VAr | unsigned word | R |
0010h | power factor | 1/1000 | unsigned word | R |
0011h | frequency | 1/100 Hz | unsigned word | R |
0012h | reserved | unsigned word | ||
0013h | reserved | unsigned word | ||
0014h | reserved | unsigned word | ||
0015h:high | station address | 1-247 | unsigned char | R/W |
0015h:low | baud rate | 1-4² | unsigned char | R/W |
001Ah | relay³ | unsigned word | R/W |
Total, export and import energy counters can erased writing 0 in total energy registers.
Value mapping, default 1.
Value | Baud rate |
---|---|
1 | 9600 Bd |
2 | 4800 Bd |
3 | 2400 Bd |
4 | 1200 Bd |
In DDS238-2 ZN/SR model the relay can be switched by 0x001A register.
Value | Relay |
---|---|
0 | Off |
1 | On |
Data format | Lenght | Byte order |
---|---|---|
char | 8 bits | |
word | 16 bits | Big endian |
dword | 32 bits | Big endian |
The meter does not understand the 'write sigle register' function code (06h), only the 'write multiple registers' function code (10h).
Try this to change slave ID https://www.domoticz.com/wiki/Python_-_Read-out_of_DDS238_kWh-meter_and_upload_to_Domoticz_and_to_PVOutput#More_than_1_kWh-meter_type_DDS238-1ZN_or_other_kWH-meters_in_the_configuration