Selected Line Name: Tower 1; Circuit 1 | |
******************* | |
As an aid in setting distance relays, the worst case positive | |
sequence line impedance, assuming untransposed phases, is: | |
0.0357 +j 0.1484 Ohms, or 0.1527 Ohms @ 76.47 degrees. | |
A zone 1 reach set to this value will not overreach the line. | |
Length: 0.41 miles | |
Surge impedance: 192.80 ohms Loading: 98.777 MW | |
Two Port Data (shunt values are for entire line) | |
-----------------Per Unit------------------ | |
Series R Series X Shunt G Shunt B | |
---------- ---------- ---------- ---------- | |
Positive Seq New 0.00018 0.00086 0.00000 0.00085 | |
Negative Seq New 0.00018 0.00086 0.00000 0.00085 | |
Zero Seq New 0.00097 0.00340 0.00000 0.00039 | |
Mutuals for PRIMARY line: Tower 1; Circuit 1 | |
and COUPLED line: Tower 1; Circuit 2 | |
------------Per Unit------------ | |
Series R Series X Shunt B B1 B2 B3 B4 | |
---------- ---------- ---------- --------- --------- --------- --------- | |
Zero Seq New 0.00072 0.00233 -0.00016 0.00000 1.00000 0.00000 1.00000 | |
******************* | |
Selected Line Name: Tower 1; Circuit 2 | |
******************* | |
As an aid in setting distance relays, the worst case positive | |
sequence line impedance, assuming untransposed phases, is: | |
0.0558 +j 0.1368 Ohms, or 0.1478 Ohms @ 67.81 degrees. | |
A zone 1 reach set to this value will not overreach the line. | |
Length: 0.41 miles | |
Surge impedance: 179.33 ohms Loading: 106.198 MW | |
Two Port Data (shunt values are for entire line) | |
-----------------Per Unit------------------ | |
Series R Series X Shunt G Shunt B | |
---------- ---------- ---------- ---------- | |
Positive Seq New 0.00029 0.00077 0.00000 0.00093 | |
Negative Seq New 0.00029 0.00077 0.00000 0.00093 | |
Zero Seq New 0.00097 0.00400 0.00000 0.00036 | |
Mutuals for PRIMARY line: Tower 1; Circuit 2 | |
and COUPLED line: Tower 1; Circuit 1 | |
------------Per Unit------------ | |
Series R Series X Shunt B B1 B2 B3 B4 | |
---------- ---------- ---------- --------- --------- --------- --------- | |
Zero Seq New 0.00072 0.00233 -0.00016 0.00000 1.00000 0.00000 1.00000 | |