ModBus read for Sinotype DDS024MR Electric Meter (https://s.click.aliexpress.com/e/_eNIqlR)
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
#!/usr/bin/env node | |
/* | |
* ModBus read for Sinotype DDS024MR Electric Meter | |
* https://s.click.aliexpress.com/e/_eNIqlR | |
*/ | |
//////////////// | |
// CONFIGURATION | |
//////////////// | |
const DEVICE = '/dev/ttyUSB0' | |
// possible values 1200, 2400, 4800, 9600, default 9600 | |
const BAUD_RATE = 9600 | |
// possible values 'even', 'odd', 'none', default 'even' | |
const PARITY = 'even' | |
// possible values 1-247, default 1 | |
const ADDRESS = 1 | |
//////////////////// | |
// END CONFIGURATION | |
//////////////////// | |
const ModbusRTU = require('modbus-serial') | |
const ieee754 = require('ieee754') | |
// create an empty modbus client | |
const client = new ModbusRTU() | |
// open connection to a serial port | |
client.connectRTUBuffered(DEVICE, { baudRate: BAUD_RATE, parity: PARITY }) | |
// set timeout, if slave did not reply back | |
client.setTimeout(500) | |
// list of meter's id | |
const metersIdList = [ADDRESS] | |
const getMetersValue = async (meters) => { | |
try{ | |
// get value of all meters | |
for(let meter of meters) { | |
// output value to console | |
console.log(`${meter}:`, await getMeterValue(meter)); | |
// wait 100ms before get another device | |
await sleep(100) | |
} | |
} catch(e){ | |
// if error, handle them here (it should not) | |
console.log(e) | |
} finally { | |
// after get all data from salve repeate it again | |
setTimeout(() => { | |
getMetersValue(metersIdList) | |
}, 1000) | |
} | |
} | |
const getMeterValue = async (id) => { | |
try { | |
// set ID of slave | |
await client.setID(id) | |
let val = await client.readHoldingRegisters(0x00, 0x12); | |
// Baud rate - 1200, 2400, 4800 or 9600 | |
const baud = ieee754.read(val.buffer, 0x00<<1, false, 23, 4) | |
// Parity - 0: even, 1: odd, 2: none | |
const parity = ieee754.read(val.buffer, 0x02<<1, false, 23, 4) | |
// Device address | |
const address = ieee754.read(val.buffer, 0x08<<1, false, 23, 4) | |
// Relay control - according to docs 1 is on, 2 is off, but I read only 0 | |
const relay = ieee754.read(val.buffer, 0x10<<1, false, 23, 4) | |
val = await client.readInputRegisters(0x00, 0x38) | |
// A phase voltage in Volts | |
const av = ieee754.read(val.buffer, 0x00<<1, false, 23, 4) | |
// B phase voltage in Volts | |
const bv = ieee754.read(val.buffer, 0x02<<1, false, 23, 4) | |
// C phase voltage in Volts | |
const cv = ieee754.read(val.buffer, 0x04<<1, false, 23, 4) | |
// A line current in Amps | |
const ac = ieee754.read(val.buffer, 0x08<<1, false, 23, 4) | |
// B line current in Amps | |
const bc = ieee754.read(val.buffer, 0x0A<<1, false, 23, 4) | |
// C line current in Amps | |
const cc = ieee754.read(val.buffer, 0x0C<<1, false, 23, 4) | |
// total active power in kWh | |
const tot_ap = ieee754.read(val.buffer, 0x10<<1, false, 23, 4) | |
// A phase active power in kWh | |
const a_ap = ieee754.read(val.buffer, 0x12<<1, false, 23, 4) | |
// B phase active power in kWh | |
const b_ap = ieee754.read(val.buffer, 0x14<<1, false, 23, 4) | |
// C phase active power in kWh | |
const c_ap = ieee754.read(val.buffer, 0x16<<1, false, 23, 4) | |
// total reactive power in kVAr | |
const tot_rp = ieee754.read(val.buffer, 0x18<<1, false, 23, 4) | |
// A phase reactive power in VAr (could be kVAr) | |
const a_rp = ieee754.read(val.buffer, 0x1A<<1, false, 23, 4) | |
// B phase reactive power in VAr (could be kVAr) | |
const b_rp = ieee754.read(val.buffer, 0x1C<<1, false, 23, 4) | |
// C phase reactive power in VAr (could be kVAr) | |
const c_rp = ieee754.read(val.buffer, 0x1E<<1, false, 23, 4) | |
// A phase power factor | |
const apf = ieee754.read(val.buffer, 0x2A<<1, false, 23, 4) | |
// B phase power factor | |
const bpf = ieee754.read(val.buffer, 0x2C<<1, false, 23, 4) | |
// C phase power factor | |
const cpf = ieee754.read(val.buffer, 0x2E<<1, false, 23, 4) | |
// frequency in Hz | |
const freq = ieee754.read(val.buffer, 0x36<<1, false, 23, 4) | |
val = await client.readInputRegisters(0x100, 2) | |
// total active electricity power in kWh | |
const tot_act = ieee754.read(val.buffer, 0x00, false, 23, 4) | |
val = await client.readInputRegisters(0x400, 2) | |
// total reactive electricity power in kVArh | |
const tot_react = ieee754.read(val.buffer, 0x00, false, 23, 4) | |
return { | |
baud, parity, address, relay, | |
av, bv, cv, ac, bc, cc, | |
tot_ap, a_ap, b_ap, c_ap, | |
tot_rp, a_rp, b_rp, c_rp, | |
apf, bpf, cpf, freq, | |
tot_act, tot_react | |
} | |
} catch(e){ | |
// if error return -1 | |
return -1 | |
} | |
} | |
const sleep = (ms) => new Promise(resolve => setTimeout(resolve, ms)) | |
// start get value | |
getMetersValue(metersIdList) |