import sys | |
sys.path.append(r"C:\DigSILENT15p1p7\python") | |
# import PowerFactory module | |
import powerfactory | |
# start PowerFactory in engine mode | |
app = powerfactory.GetApplication() | |
user = app.GetCurrentUser() | |
# activate project | |
project = app.ActivateProject("Nine Bus System") | |
prj = app.GetActiveProject() | |
ldf = app.GetFromStudyCase("ComLdf") | |
ini = app.GetFromStudyCase('ComInc') | |
sim = app.GetFromStudyCase('ComSim') | |
Shc_folder = app.GetFromStudyCase('IntEvt'); | |
terminals = app.GetCalcRelevantObjects("*.ElmTerm") | |
lines = app.GetCalcRelevantObjects("*.ElmTerm") | |
syms = app.GetCalcRelevantObjects("*.ElmSym") | |
Shc_folder.CreateObject('EvtSwitch', 'evento de generacion'); | |
EventSet = Shc_folder.GetContents(); | |
evt = EventSet[0]; | |
evt.time =1.0 | |
evt.p_target = syms[1] | |
ldf.iopt_net = 0 | |
ldf.Execute() | |
elmres = app.GetFromStudyCase('Results.ElmRes') | |
for terminal in terminals: | |
elmres.AddVars(terminal,'m:u','m:phiu','m:fehz') | |
for sym in syms: | |
elmres.AddVars(sym,'s:xspeed') | |
ini.Execute() | |
sim.Execute() | |
evt.Delete() | |
comres = app.GetFromStudyCase('ComRes'); | |
comres.iopt_csel = 0 | |
comres.iopt_tsel = 0 | |
comres.iopt_locn = 2 | |
comres.ciopt_head = 1 | |
comres.pResult=elmres | |
comres.f_name = r'C:\Users\jmmauricio\hola.txt' | |
comres.iopt_exp=4 | |
comres.Execute() |
Hi Everyone, did anybody know how can i create static generator objects in my project and then need to read date from csv file in order to give every photovoltic (static generator) their power and other properties??
Hello, . I'm trying to implement rms simulation via python code and I ran into a problem. I want to extract the value of a variable at a specific moment in time, but I don't know how to do it. can someone help me please? Regards!
Hi
I want to add a shunt element to a bus. How can I do it?
Thanks.
When I close powerfactory, I run the following python script:
import sys sys.path.append( r"C:\Program Files\DIgSILENT\PowerFactory 2022\Python\3.10") if __name__ == "__main__": import powerfactory app = powerfactory.GetApplication() if app is None: raise Exception('getting Powerfactory application failed')
Error reported:
Process finished with exit code -1073741819 (0xC0000005)
Tried many methods to no avail, if you have a similar situation and successfully solved it, or if you have other suggestions, please let me know, thank you for your help, it is greatly appreciated
import os
os.environ["PATH"]=r"C:\DIgSILENT\PF 2023_SP5"+os.environ["PATH"]
import sys
sys.path.append(r"C:\DIgSILENT\PF 2023_SP5\Python\3.8")
#IMPORTAR LA APLICACION
try:
import powerfactory as pf
app = pf.GetApplication()
app.Show()
outputWindow = app.GetOutputWindow()
outputWindow.Print(pf.OutputWindow.MessageType.Plain, "Hello World!")
except Exception as e:
print("Error corregir",e)
Only close powerfactory, If powerfactory is run, Engine mode with Digrcom.
I have Digsilent 15.1 and I want to extract each line losses in load flow simulation, if python needed, what version and what i need to install, I am new thank you for your help. Oh I also tried using DPL but it always ends up in missing semicolon even if its there, code from chatgpt.
@rimmetz17
You could only use python 3.3 which is obsolete. You should upgrade your powerfactory
@rimmetz17 You could only use python 3.3 which is obsolete. You should upgrade your powerfactory
which version is available for python?
For python 3.3 you can download it if you Google it. However, for supporting package (numpy, pandas), it quite difficult to search it.
If you can upgrade the powerfactory, I recommend the latest one (powerfactory 2024) or at least powerfactory 2020 (due to my first time using python for powerfactory)
I already got pf2021 and currently using python 3.9, but i have trouble "cannot connect to powerfactory application". do you have any reference step by step to follow? i am currently using chatgpt as guide
Managed to get the Ploss data from attribute c:Ploss, does anyone know how to get the active power each line? tried using Pline, Plinu(from chatgpt), P, none of them works
thank u so much for the replies.
now I am wondering why my calculations are differ from the simulation result. I calculate Ploss using I^2 R, which R replaced by Z (R+XL for <80km line), Z calculation are similar than in simulation "resulting values" in line data (6.8 vs 6.78 ohm), Current are similar (both 85A) since Power are similar (both 21-22 MW), using I^2 Z, simulation differ up to 2x-4x value of calculation.
I don't know how the procedure that you are using to calculate Ploss. However, If you only calculate Ploss(active power losses), you should using I^2 R, not I^2 Z.
Hi. I want to know if someone can help me in a issue that I´m having on Digsilent 2023... I want to know if it is posible to modify a setpoint value of a controller of a STATCOM during a RMS simulation; specifically when one specific line trips off (Meaning that the system would be running in N-1 condittions), for instance, at that moment when N-1 scenario occurs, instead of a setpoint value of 1 pu voltage at certain busbar, the statcom change that setpoint to look up for 0.98 pu. voltage.... Please if you can help me I´ll appreciate it.